Coherence in synchronizing power networks with distributed integral control

Martin Andreasson,Emma Tegling,Henrik Sandberg,Karl H. Johansson
DOI: https://doi.org/10.1109/cdc.2017.8264613
2017-12-01
Abstract:We consider frequency control of synchronous generator networks and study transient performance under both primary and secondary frequency control. We model random step changes in power loads and evaluate performance in terms of expected deviations from a synchronous frequency over the synchronization transient; what can be thought of as lack of frequency coherence. We compare a standard droop control strategy to two secondary proportional integral (PI) controllers: centralized averaging PI control (CAPI) and distributed averaging PI control (DAPI). We show that the performance of a power system with DAPI control is always superior to that of a CAPI controlled system, which in turn has the same transient performance as standard droop control. Furthermore, for a large class of network graphs, performance scales unfavorably with network size with CAPI and droop control, which is not the case with DAPI control. We discuss optimal tuning of the DAPI controller and describe how internodal alignment of the integral states affects performance. Our results are demonstrated through simulations of the Nordic power grid.
What problem does this paper attempt to address?