The Design and CFD Simulation of a New Spent Fuel Pool Passive Cooling System

Cheng Ye,Minglu Wang,Mingguang Zheng,Zhengqin Xiong,Ronghua Zhang
DOI: https://doi.org/10.1115/icone21-15040
2013-07-29
Abstract:Due to the safety issues arising from the Fukushima accident, a novel completely passive spent fuel pool cooling system is proposed using the high-efficiency heat pipe cooling technology that is available in an emergency condition such as a station blackout. This cooling system’s ability to remove the decay heat released by the spent fuel assemblies is evaluated by a computational fluid dynamics (CFD) simulation. The spent fuel pool of CAP1400 (a passive PWR developed in China) is selected as the reference pool, and the passive cooling system is designed for this spent fuel pool. The pool with the passive cooling system is simulated using Fluent 13.0 with 4 million meshes. Four different cases have been studied, and some notable results have been obtained through this work. The simulation results reveal that the passive cooling system effectively removes the decay heat from the SFP with the storage of 15-year-old spent fuel assemblies with emergency reactor core unloading and prevents the burnout of the fuel rods. The results indicate that the water in the SFP will never boil, even in a severe accident with a lack of emergency power and outside aid.
What problem does this paper attempt to address?