Fault Diagnosis for Terminal of 10kV XLPE Cable based on the Improved M-training Algorithm

Dongyang Wang,Xiangyu Zhang,Lei Guo,Yupeng Hu,Hanqing Ma,Bokai Liu,Lijun Zhou
DOI: https://doi.org/10.1109/jsen.2024.3367871
IF: 4.3
2024-01-01
IEEE Sensors Journal
Abstract:The 10kV Cross-linked polyethylene (XLPE) cables are widely used in urban distribution networks, of which the cable terminals are the weak links. In this paper, the fault diagnosis for terminal of 10kV XLPE cable was studied based on the improved M-training algorithm. First, the cable terminal samples with typical defects were prepared, and partial discharge (PD) data were obtained by the experiment platform. Then, the features of PD data were extracted by using the fusion of the texture features of gray gradient co-occurrence matrix (GGCM) and Goes–Markov random field (GMRF). Afterwards, the M-training algorithm was improved from two aspects: 1) four different classifiers were used instead of the four identical classifiers in conventional algorithm; 2) to overcome the effects of the error rates of unlabeled samples on classification error, the classification error in the M-training algorithm was optimized. Based on the improved M-training algorithm, the diagnosis method for 10kV XLPE cable terminal was proposed. Finally, the proposed method was verified: the confusion matrix was used to express the recognition results, and the recognition effects of different schemes were analyzed based on four indicators (i.e., accuracy, sensitivity, specificity, and F1-score). The results show that the recognition accuracy rate was 97.8%, with sensitivities of 98.1%, 97.9%, and 97.4%, and specificities exceeding 97%, and F1-scores were 97.6%, 97.9%, and 97.9%, respectively.
engineering, electrical & electronic,instruments & instrumentation,physics, applied
What problem does this paper attempt to address?