Measurement of high-boiling point fire suppressant concentration using an improved differential pressure method

Hui Shi,Song Lu,Weitong Ma,Heping Zhang
DOI: https://doi.org/10.1016/j.measurement.2022.110818
IF: 5.6
2022-03-01
Measurement
Abstract:Concentration measurement technology for fire suppressants is important for assessing the effectiveness of aircraft fire-suppression systems. In this study, based on the differential pressure method, a concentration measurement model for high-boiling point fire suppressants was established. To validate the theory and evaluate the sensing performance, concentration experiments involving perfluorohexanone were conducted, and the effects of the operating temperature and geometric dimensions of the sensing part on the concentration measurements were analysed. The results indicated that the absolute error of the concentration measurements for perfluorohexanone was < 0.2% and that the response time did not exceed 0.22 s within the volume concentration range of 0%–20%. The restrictor size affected on the response time and sensitivity. Additionally, a temperature correction model was established. This study proposes an improved differential pressure method for concentration measurement of high-boiling point halon-alternative fire suppressants, and the measurement performance can satisfy application requirements.
engineering, multidisciplinary,instruments & instrumentation