Sag and Tension Calculations for High-Voltage Overhead Line Conductors

Marian Kampik,Paweł Kubek,Beata Krupanek,Ryszard Bogacz
DOI: https://doi.org/10.3390/en17122967
IF: 3.2
2024-06-17
Energies
Abstract:Overhead lines are used to transmit electricity from where it is generated to the receiving stations. The correct design of an overhead line affects public safety, because it should ensure the required clearances between conductors and the ground and objects located in the space under the overhead line. The temperature of conductors in overhead lines depends on the load current and weather conditions, and affects the sag and tension of the conductors. Calculations of sags and tensions of overhead conductors can be performed using simplified calculation methods that do not consider insulator sets. In some situations, this approach may cause calculation errors. This article discusses algorithms for calculating overhead conductor tensions and sags in the tensioning sections of high-voltage overhead lines, accounting for and excluding insulator sets. The analysis is carried out for different lengths of tensioning sections and various thermal and mechanical states of the conductors.
energy & fuels
What problem does this paper attempt to address?
### Problems Addressed by the Paper The paper primarily focuses on the calculation of sag and tension in high-voltage overhead line conductors, with particular emphasis on the impact of insulator sets under different temperature and mechanical conditions. **Specific Issues Include:** 1. **Limitations of Simplified Methods**: - Simplified calculation methods typically do not consider the impact of insulator sets, which can lead to significant calculation errors in certain situations. - Especially under high operating temperatures and uneven span lengths, simplified methods may not be accurate enough. 2. **Impact of Insulator Sets**: - The presence of insulator sets changes the actual suspension point of the conductor, thereby affecting the calculation of sag and tension. - In short-span situations, the weight and size of the insulator sets are relatively large compared to the conductor, making their impact more significant. 3. **Development of Accurate Calculation Methods**: - An accurate calculation model is proposed, considering the length and mass of the insulator sets to improve the accuracy of sag and tension calculations. - This model can better simulate the behavior of the conductor under different operating conditions, ensuring compliance with safety distance requirements. Through these studies, the paper aims to develop a method that can accurately predict the sag and tension of high-voltage overhead line conductors, ensuring public safety and optimizing line design.