Power Compatibility of Induction Motors in Industrial Grids Containing Synchronous Generators

Yuriy Varetsky,Michal Gajdzica
DOI: https://doi.org/10.3390/en17051066
IF: 3.2
2024-02-24
Energies
Abstract:Starting an induction motor causes voltage sag in the industrial grid that may disturb the operation of grid equipment. Direct-on-line starting is the simplest and most cost-effective method for starting induction motors, but also the most problematic. Large industries often use internal power plants with synchronous generators and starting powerful motors may impact the generator operations. The synchronous generators could be operated with the automatic or manual mode of voltage control. As the operation experience proves, the generator voltage control mode has a significant impact on the transient behaviours in the industrial power grid when starting a large induction motor. This article presents a case study of the synchronous generator tripping within a true medium-voltage industrial grid during the direct-on-line starting of a large induction motor driving the feed water pump. An analysis of the generator protection logs after the tripping showed that the synchronous generator was controlled in manual mode and its protection relay settings were exceeded. The transients initiated by induction motor starts were studied for possible configurations and operating conditions of the grid using a model developed on the Matlab/Simulink Software platform. The simulations have shown that concern about starting large motors in industrial grids containing internal synchronous generators needs to be solved considering the grid configurations and the coordination of generator protection and control devices.
energy & fuels
What problem does this paper attempt to address?
This paper mainly discusses the problems and solutions encountered when starting an induction motor in an industrial power grid containing synchronous generators. ### Problems the Paper Attempts to Solve 1. **Voltage Drop Issue**: Starting an induction motor can cause a voltage drop in the industrial power grid, which may interfere with the normal operation of grid equipment. 2. **Impact on Synchronous Generator Operation**: Large industrial facilities often have internal power plants that include synchronous generators. Direct-On-Line (DOL) starting of powerful induction motors may affect the operation of these synchronous generators. 3. **Generator Control in Manual and Automatic Modes**: Synchronous generators can operate in automatic or manual voltage control modes. Practical experience shows that the control mode of the generator significantly affects its transient behavior when starting large induction motors. 4. **Protection Device Setting Issues**: In one incident mentioned in the study, the synchronous generator was operating in manual control mode, and its protection relay settings were exceeded, causing the synchronous generator to trip. 5. **Coordination of Generator Protection and Control Systems**: The paper emphasizes the need to consider grid configuration and coordinate the protection and control systems of synchronous generators to address issues arising from starting large motors. ### Summary Through a case study, the paper analyzes a situation in a real medium-voltage industrial power grid where Direct-On-Line starting of a high-power induction motor driving a feedwater pump caused the synchronous generator to trip. Researchers used the Matlab/Simulink software platform to model and simulate the transient behavior of the grid under different configurations and operating conditions to explore potential problems and solutions when starting large induction motors. The focus is on understanding the interaction between grid configuration, synchronous generator protection, and control systems, and how appropriate coordination can ensure stable grid operation.