Control Method of Static Var Generator to Aid Direct Starting of Large Induction Motor in Offshore Oil-Rig Power System

Che WEI,Yipeng DONG,Jianfeng WANG,Guofeng LIU,Qiang LI,Xiaorong XIE
2014-01-01
Abstract:The direct starting of large induction motors such as water-injection pumps in an independent offshore oil-rig power system will result in severe problems, for instance, sharp increase of reactive power, deep drop of bus voltage, drop-off of load, or even trip of overloaded generators. To handle these problems, an improved dynamic var control method of static var generator(SVG) was presented. The method, as an improvement on the conventional var/voltage regulation, has newly developed control functions of motor-starting var compensation and switch control, by which, the motor and SVG are controlled to go through the states of pre-starting, start-preparation, motor-starting and start completion successively and smoothly. The proposed method is applied to the Southwest Wei offshore power system on the South China Sea. The simulation results show that it can provide sufficient dynamic var support for the direct starting of large induction motors and the bus voltage is maintained, the safe operation of gas-turbine generator and load is guaranteed.