Grounding resistance model considering propagation time between grounding electrodes

Shozo Sekioka
DOI: https://doi.org/10.1016/j.epsr.2024.110524
IF: 3.818
2024-06-09
Electric Power Systems Research
Abstract:The velocity of electric field in the soil is sufficiently lower than that in the air. Conventional grounding resistance models based on an electric circuit theory ignore the propagation time between grounding electrodes (GEs). If the GEs are connected using an aerial lead conductor, the propagation time along the lead conductor is apparently different from that along a grounding conductor (GC) in the soil. The propagation time of mutual grounding resistance between GEs should be considered in accurate lightning surge analysis. This paper proposes a simulation model of the mutual grounding resistance considering the propagation time between GEs.
engineering, electrical & electronic