Abstract:Ester liquids are environmentally friendly insulating oils, and they can be used as an alternative to mineral oil in transformers, even though in most countries spills of ester oils must be treated like spills of mineral oil. Furthermore, the breakdown characteristics of ester liquids are worse than those of mineral oils in heterogeneous electric fields. In this paper, we present a comprehensive experimental research on both positive and negative lightning impulse breakdown properties in point-plane geometries with gaps varying from 1 mm to 50 mm. The breakdown voltages and streamer velocities of five kinds of ester liquids, including natural ester, synthetic ester, and three kinds of single component esters have been measured. The results show that the double bonds have no effect on the breakdown voltage of ester liquids. The average streamer velocities of mono-esters are faster than that of other esters under positive polarity, and the breakdown voltages of all esters are close.
energy & fuels
What problem does this paper attempt to address?
### Problems Addressed by the Paper This paper primarily explores the lightning impulse breakdown characteristics of different ester liquids in non-uniform electric fields. Specifically: 1. **Research Background and Objectives**: - Ester liquids, as an environmentally friendly insulating oil, can replace mineral oil in transformers. However, in non-uniform electric fields, the breakdown characteristics of ester liquids are not as good as those of mineral oil. - Currently, there is limited research on the breakdown voltage of ester liquids with different molecular structures under lightning impulse. - Therefore, this paper aims to experimentally study the lightning impulse breakdown voltage and streamer velocity of different ester liquids (including natural esters, synthetic esters, and mono-component esters) in non-uniform electric fields. 2. **Experimental Design**: - Five types of ester liquids (synthetic ester Midel 7131, rapeseed-based natural ester, glycerol trioleate, ethyl oleate, ethyl linoleate) and one traditional mineral oil were selected for comparative experiments. - The experiments used a point-plane electrode system and measured the positive and negative lightning impulse breakdown voltage and streamer velocity at different gap distances (1 mm to 50 mm). 3. **Main Findings**: - At 1-15 mm gaps, the positive lightning impulse breakdown voltage of ester liquids varied significantly with no obvious pattern; at 25 mm and 50 mm gaps, the breakdown voltage of mineral oil was slightly higher than that of ester liquids. - Under negative lightning impulse, the breakdown voltage of mineral oil was always higher than that of ester liquids, and the difference increased with the gap distance. - The ester bonds in the molecular structure had a significant impact on the negative lightning impulse breakdown voltage, especially for synthetic esters, which had the lowest breakdown voltage due to the presence of more ester bonds. ### Summary Through systematic experimental research, this paper reveals the differences in lightning impulse breakdown characteristics of different ester liquids in non-uniform electric fields and discusses the impact mechanism of molecular structure on their breakdown voltage. This is of great significance for optimizing the performance of ester liquids in practical applications.