Experimental research on inerting characteristics of carbon dioxide used for fire extinguishment in a large sealed space

Liang Ge,Yimin Shao,Yinjun Wang,Guangxun Zhang,Zujing Zhang,Lin Liu
DOI: https://doi.org/10.1016/j.psep.2020.06.005
IF: 7.8
2020-10-01
Process Safety and Environmental Protection
Abstract:A large sealed space and its monitoring system of environmental information including the temperature, pressure and various gas contents were built.Experiments on inerting characteristics of carbon dioxide including fire extinguishment, accumulation and distribution as well as cooling were carried out firstly.The critical oxygen concentration of extinguishing the fire sources and the corresponding carbon dioxide concentration were determined precisely.The layering law of gas component concentrations in the stabilized gas and cooling function of liquid direct injection were proved quantitatively.To accurately guide the quantitative injection of carbon dioxide for extinguishing the fire or diluting the accumulated toxic gases, 26 sensing devices used for detecting the multiple environmental parameters were firstly laid inside and outside of 210 m<sup>3</sup> large sealed space, then each signal output from the sensing devices was transmitted successively to the A/D conversion module and the server with signal acquisition and analysis software, so the experimental research on inerting characteristics of carbon dioxide in different physical forms in this sealed space were carried out by using the mobile liquid storage and injection equipment, including fire source extinction, and accumulation and distribution of gas components, as well as cooling. Results show that: (1) For wood and gasoline, the critical oxygen concentration of combustion 16.98 % and the corresponding carbon dioxide concentration 28.6 % were determined comprehensively; (2) The concentration layering law in the stabilized gas was proved to be inconsistent with theoretical correspondence between specific gravity and height; (3) For direct liquid injection and gas perfusion at 2.2 MPa, the average temperature difference were 13.8 °C and 0.3 °C respectively, so the temperature drop characteristic of liquid injection was proved, and its optimal cooling distance from the nozzle is further determined from 5.6 m to 11.2 m.
engineering, environmental, chemical
What problem does this paper attempt to address?