Experimental study on fire suppression performance of the high pressure water mist in the engine room of an offshore platform

Yan Huo,Miao Chen,Tian Li,Gao-Wan Zou,Hui Dong
DOI: https://doi.org/10.1016/j.jlp.2023.105052
IF: 3.916
2023-07-01
Journal of Loss Prevention in the Process Industries
Abstract:The total flooding application water mist system is a new type of environmentally-friendly fixed extinguishing system. The optimizing design can improve its fire extinguishing performance. At present, the water mist fire extinguishing system in the engine room of the offshore deepwater semi-submersible support platform has not attracted sufficient attention. In this paper, the water mist in the engine room of a deepwater semi-submersible support platform was studied. It contains the effect of water mist on the heat absorption and oxygen insulation of diesel pool fires. The applicable parameters of the water mist fire extinguishing system were also determined. Moreover, based on the shielding of the fire source in the engine room and the different requirements for water mist extinguishing parameters, a hierarchical multi-parameter combined high-pressure water mist fire extinguishing system was proposed. In the full-scale experimental engine room model, according to the fire extinguishing experiments for diesel pool fires with different areas, this kind of hierarchical multi-parameter water mist system is very effective on shielded and non-shielded fires. In addition, it is still effective even in a non-closed environment coupled with smoke exhausting.
engineering, chemical
What problem does this paper attempt to address?