Thermal-aware layout planning for heterogeneous datacenters

Reza Azimi,Xin Zhan,Sherief Reda
DOI: https://doi.org/10.1145/2627369.2627639
2014-08-11
Abstract:Cooling power represents a significant portion of total power consumption in datacenters. Heterogeneous datacenters deploy clusters of servers with different hardware configurations, each offering its own performance and power characteristics. We observe that heterogeneous datacenters offer a unique opportunity to reduce cooling power through appropriate planning. In this paper we formulate the problem of rack layout for planning of heterogeneous datacenters, where the goal is to identify the best locations of the server racks with different hardware capabilities to improve the supply temperatures of the CRAC units and the total cooling power. We provide optimal solutions that take into account the impact of varying utilizations of datacenters and job scheduling methods. Using state-of-the-art thermal modeling tools, we prove that our methods lead to datacenter layouts with significant improvements in cooling power reduction, between 15.5%-38.5% based on the datacenter utilizations and an average of 28.3% without any negative side effects.
What problem does this paper attempt to address?