Experimental analysis on performance assessment of a hybrid double cross flow tube arrangement in a shell and tube heat exchanger

D. P. Sam Solomon,V. Selladurai,A. S. Krishnan
DOI: https://doi.org/10.1007/s12206-021-1247-z
IF: 1.81
2022-01-01
Journal of Mechanical Science and Technology
Abstract:The article presents the evolution of a novel configuration of tube placements in a shell and tube heat exchanger (HX). A CFD analysis on a double cross flow arrangement of tubes reveals improved mixing of the shell-fluid which is expected to increase heat transfer. This arrangement was modified for easier manufacture and maintenance, which led to the hybrid double cross flow (HDCF) arrangement. Experiments were carried out in the HDCFHX, for parallel and counter flows, to compare its performance against the conventional staggered arrangement. The HDCFHX comprises composite bundles of three and four tubes. The three-tube bundle is arranged in a staggered manner to themselves and orthogonal to the four-tube bundle. Ambient air at of 32 °C was used as the shell-fluid for Reynolds number ranging from 500 to 1000, for a fixed flow rate of 0.6 kg/min of water entering the tubes at 85 °C. This arrangement was observed to enhance the heat transfer with relatively lesser increase in pressure drop. The HDCFHX gave a significant improvement in heat transfer rate per pressure drop of 17 % to 38 %, vis-à-vis the conventional staggered arrangement in the parallel mode. The counter flow mode overly exhibited a similar trend, wherein the increase in this ratio varied from 8.5 % to 27.5 %.
engineering, mechanical