Impact of Fuel Type on Fire Dynamics in Mechanically Ventilated Compartment as a Consequence of Closing Inlet Vent

Brady Manescau,Hui-Ying Wang,Jean Pierre Garo,Bruno Coudour,Lahna Acherar
DOI: https://doi.org/10.1007/s10694-021-01204-z
IF: 3.605
2022-01-24
Fire Technology
Abstract:In the industrial environments, one of the ways to prevent the spread of harmful fire by-products to adjacent compartments via ventilation networks consists in applying an Inlet Valve Closure procedure. A theoretical research by means of the experiments and the physics-based models is performed to investigate the consequences of closing air intake on fire behavior in the mechanically ventilated compartment. In well-ventilated conditions, the strategy of closing inlet vent can be considered as a positive factor with a reduction in HRR regardless of fuel type such as heptane or dodecane. In under-ventilated conditions, replacing heptane by dodecane with a higher boiling point leads to a change in fire dynamics regime from a ventilation to fuel controlled fire. Closing inlet vent contributes to a faster heptane fire growth with an increase in theoretical HRR by a factor of 5%, and however, exhaust of the ventilation controlled fire occurs more easily due to a reduction in combustion efficiency by a factor of 30%. However, for the dodecane fire, closing inlet vent facilitates a reduction in HRR over a longer burning period. Air entering the compartment follows closely the fluctuations of the fire induced pressure as a result of strong coupling process between drop in pressure and inlet flow rate. For the heptane fire in vitiated air environment, the impact of stopping inlet vent on the peak of unburnt species concentration seems negligible. Dodecane with a longer carbon chain produces more unburnt gases than heptane, and turning off air intake results in a reduction in unburnt species. Occurrence of flame extinction in the vitiated air enclosure makes a sudden supply of fresh air from dilution duct with an oxygen concentration of about 15%, ideal condition for triggering an eventual auto-ignition of a fuel–air mixture. With regarding the delay time for an ignition risk of unburnt pyrolyzates, the heptane fire appears more dangerous by closing inlet vent. For the dodecane fire, stopping inlet vent contributes to a prolongation in ignition delay time of unburnt pyrolyzates.
materials science, multidisciplinary,engineering
What problem does this paper attempt to address?