Noise Reduction of a Fan and Air Duct by Using a Plenum Chamber Based on ASHRAE Guidelines

Farhad Forouharmajd,Parvin Nassiri
DOI: https://doi.org/10.1260/0263-0923.30.3.221
2011-09-01
Abstract:Noise propagates from sources through air distribution duct systems, structures, and combinations of paths, reaching the occupants. A plenum chamber is similar to a dissipative silencer, but it is also similar to a small room with a noise source in one wall. The dimensions of the plenum chamber are usually larger than the wavelength of the sound being attenuated. Above the cutoff frequency, as defined by the plenum's inlet duct dimensions, the wavelength of sound is small compared to the characteristic dimensions of the plenum. All values are in terms of sound pressure level with “A” frequency weighting and “slow” time weighting measured by a B&K 2231 sound level meter and 1625 analyzer. Input and output in this compartment as opposed to a two-sided compartment was based on the ASHRAE instructions on the frequency of cutoff. This frequency indicates that the chamber dimensions that channel input and output frequencies higher than 436 Hz will be effective in reducing noise.
acoustics