Energy saving potential of low-e coating based retrofit double glazing for tropical climate

Sivanand Somasundaram,Alex Chong,Zhang Wei,Sundar Raj Thangavelu
DOI: https://doi.org/10.1016/j.enbuild.2019.109570
IF: 7.201
2020-01-01
Energy and Buildings
Abstract:Double glazed facades are a well established feature for buildings located in cold ambient climate. In tropical climate there has been some penetration of Double Glazing Units (DGU) to reduce air-conditioning load. However, for existing buildings with older glass (usually having lower thermal insulation and higher solar transmission) a simple retrofit solution is to attach a low-e (hard coat) coated glass internally in the building without an explicit air tight seal. To analyse the proposed retrofit double glazing solution, experiments were conducted in a fully instrumented living lab to observe the performance viz: energy saving potential, Lux levels, and mean radiant temperature. Simulation using an energy model was conducted to estimate the annual energy savings. It is observed that retrofit hard coat low-e double glazing saves up to about 9 % of daily energy consumption of Air conditioners (with annual average of 3% for Singapore weather conditions), when installed on all three sides (SE,NW,NW), for clear glass with window to wall ratio of 20 % and air change rate of 1 ACH. For the same conditions the annual average energy savings can go up to 7.5 % when installed on an existing grey tinted glass.
energy & fuels,construction & building technology,engineering, civil
What problem does this paper attempt to address?