On the Design of Sound Absorbing Ducts

U. Ingård,J. J. Baruch,L. L. Beranek,S. Labate
DOI: https://doi.org/10.1121/1.1917289
1951-01-01
The Journal of the Acoustical Society of America
Abstract:General design charts for square and circular sound absorbing ducts have been developed by an application of Morse's theory for the transmission of sound inside pipes. These charts have been developed specifically for ducts with all four walls lined with an absorbing material with or without an air space behind it. Interesting results of this study are that attenuations of 15 to 20 db per wavelength can be obtained over a frequency range of about one-half octave and that by scaling the size of the duct and the impedance of the acoustical material on the side walls this peak in attenuation may be placed at any desired frequency. Measurements on ducts ranging in size from 8×8 in. to 4×4 ft. show that the measured attenuation curves result in somewhat higher values of attenuation above and below the peak value and a slightly lower value at the peak than are calculated from the charts. For those ducts in which an air space is used behind the absorbing inner wall, the partitioning of the air space plays an important part. In order to realize the calculated values of attenuation, the partitions should be spaced at intervals of about one-quarter wavelength.