An Optimized Fault-Ride-Through Control Strategy of Hybrid MMC with Fewer FBSMs

Yue Chen,Chenglin Ren,Junyi Sheng,Jinyu Wang,Yuebin Zhou,Wanyu Cao,Runtian Ding,Wujun Wang
DOI: https://doi.org/10.3390/electronics13101797
IF: 2.9
2024-05-07
Electronics
Abstract:The modular multilevel converter (MMC) has many advantages of low switching losses, good harmonic performance and high modularity structure in state-of-the-art HVDC applications. The full-bridge submodules (FBSMs) of the hybrid MMC can inherently output negative voltage to absorb fault currents, and consequently the hybrid MMC can ride through severe DC faults without blocking. During the DC fault-ride-through process, the submodule capacitor voltage and arm current of the MMC will be temporarily increased. These characteristics limit the proportion of the FBSMs, which should not be too low and thus increase the cost and operating losses of the hybrid MMC. In this paper, an improved sorting algorithm of SM capacitor voltage is established, and a novel virtual damping control strategy is proposed that can effectively suppress the increase in submodule capacitor voltage and arm current of the hybrid MMC during the DC fault-ride-through process. By adopting this optimization control, the proportion of FBSMs can be reduced significantly without deteriorating the fault-ride-through capability or safety of the MMC. The effectiveness of the proposed control is verified by careful theoretical analysis and detailed simulation results.
engineering, electrical & electronic,computer science, information systems,physics, applied
What problem does this paper attempt to address?
The problem that this paper attempts to solve is how to maintain good Fault - Ride - Through (FRT) capability while reducing the number of Full - Bridge Submodules (FBSMs) in the Hybrid Modular Multilevel Converter (Hybrid MMC). Specifically, the paper focuses on effectively suppressing the increase in sub - module capacitor voltages and arm currents through an optimized control strategy during a DC fault, thereby reducing the requirement for the proportion of FBSMs, and cutting down costs and operating losses. ### Background and Problems 1. **Background**: - The Modular Multilevel Converter (MMC) has the advantages of low switching losses, good harmonic performance, and a highly modular structure in High - Voltage Direct - Current (HVDC) applications. - Full - Bridge Submodules (FBSMs) can output negative voltages to absorb fault currents, enabling the Hybrid MMC to ride through severe DC faults without blocking. - During the DC fault - ride - through process, the sub - module capacitor voltages and arm currents will increase temporarily, which limits the proportion of FBSMs from being too low; otherwise, it will increase costs and operating losses. 2. **Problems**: - How to maintain good DC fault - ride - through capability and safety while reducing the number of FBSMs? - How to effectively suppress the increase in sub - module capacitor voltages and arm currents to improve the economy and reliability of the system? ### Solutions The paper proposes an optimized fault - ride - through control strategy, mainly including two aspects: 1. **Optimized Sorting Algorithm**: - By improving the sorting algorithm for sub - module capacitor voltages, selectively inserting Half - Bridge Submodules (HBSMs), when the arm output voltage reference value is greater than 0 and the arm current is charging, using HBSMs to absorb part of the charging current, thereby effectively reducing the peak capacitor voltage of FBSMs. 2. **Virtual Damping Control**: - Introduce virtual damping control. By adding virtual inductors in the DC current control station and the DC voltage control station, effectively suppress the development of DC fault currents. Specifically, the virtual damping control makes the DC modulation ratio decay rapidly to 0 after the DC fault occurs through introducing a feed - forward element, thereby suppressing the growth of the fault current. ### Conclusions Through the above - mentioned optimized control strategy, the proportion of FBSMs can be significantly reduced without reducing the fault - ride - through capability and safety, thereby reducing the cost and operating losses of the Hybrid MMC. The paper verifies the effectiveness of the proposed control strategy through theoretical analysis and detailed simulation results.