Pilot Testing and Engineering Application of O 3 /H 2 O 2 Process for 2-Methylisoborneol and Geosmin Removal in Drinking Water Treatment
Jinyu Peng,Quanyong Wang,Zhenbang Li,Xiaomao Wang,Shuming Liu,Yujiang Li,Yuefeng Xie,Yixuan Li
DOI: https://doi.org/10.1016/j.jwpe.2024.105140
IF: 7
2024-01-01
Journal of Water Process Engineering
Abstract:Microorganisms in source water, including algae, actinomycetes and other microbes, produce secondary metabolites during growth, particularly 2-methylisoborneol (2-MIB) and geosmin (GSM), which emerge as the primary contributors to taste and odor issues in drinking water. Although the conventional ozone (O-3) oxidation process has been widely adopted to address the odor issue, it frequently exhibits inadequate removal efficiency for 2-MIB and GSM, and presents the risk of bromate formation exceeding regulation limit when processing bromine-enriched water. In this study, a pilot study applying the O-3/H2O2 advanced oxidation process (AOP) was conducted to overcome the above problems. The influence of variables, including O-3 dosage, O-3/H2O2 ratio, etc., on the removal efficiency of 2-MIB, GSM, natural organic matter as the permanganate index (PI), and bromate formation was investigated, and compared with the conventional ozonation process. According to the pilot-scale experiments, the O-3/H2O2 AOP demonstrated remarkable efficacy in effectively eliminating odorous substances and inhibiting bromate formation. The full-scale application of the O-3/H2O2 AOP at a 120,000 m3/d water plant in Shandong, China also showed that while the 2-MIB and GSM concentrations in raw water were up to 260 and 33 ng/L, respectively, the treated water had 2-MIB and GSM concentrations <10 ng/L, which fulfills the "Standards for Drinking Water Quality" of China (GB 5749-2022). Meanwhile, bromate remained undetectable.