Abstract:In order to solve the problem that the traditional fault location scheme is no longer suitable after the distributed power supply is connected to the distribution network, this paper presents a fault location method of cable line which is not affected by multiple power sources. By using the feature extraction and classification function of convolutional neural network (CNN), the deep learning of various active distribution network cable structures and fault transient voltage and current characteristics under different fault types can realize automatic line selection. On this basis, the single-ended traveling wave positioning method is used for accurate positioning. In this paper, the fault data obtained by Simulink simulation is used as the training set and the test set. The test results show that the location error is controlled within 0.5%, and this method can realize the fault location well in the case of unknown fault and unknown distributed power access.