Numerical Study of Condensation Heat Transfer Characteristics of R134a/R290 and R134a/R1270 Refrigerant Blends As Alternatives to Replace R404A

Min-Qiang Zeng,Lin-Geng Zou,Zhao-Rui Peng,Xin-Rong Zhang,Jing Li
DOI: https://doi.org/10.1016/j.applthermaleng.2024.122644
IF: 6.4
2024-01-01
Applied Thermal Engineering
Abstract:R404A needs to be replaced due to its higher GWP in the context of green development. In this study, M1 (R134a/R290, 55/45) and M2 (R134a/R1270, 43/57) were proposed to replace R404A refrigerant. The thermodynamic properties were compared. The heat transfer and pressure drop characteristics of condensation for R404A, M1 and M2 inside horizontal microtube (D = 1 mm) at saturation temperature of 40celcius were investigated numerically. The results showed that the COP of M1 and M2 were higher than that of R404A, while the GWP of M1 and M2 is 81.83 % and 85.79 % lower than that of R404A, respectively. The heat transfer coefficients and pressure gradients increase with increasing mass flux and vapor quality, the heat transfer coefficient of M1 and M2 were on 50 - 55 % and 78 - 80 % higher than that of R404A. However, the pressure gradients of M1 and M2 were on 95 - 110 % and 105 - 115 % larger than that of R404A. The liquid film thicknesses of M1 and M2 were smaller than that of R404A. M1 and M2 could be used as low GWP alternatives to R404A with regard to thermodynamic performance and heat transfer properties. The results of the study have important guiding value for the replacement of R404A.