Abstract:Modular solid-state transformers (SSTs) are the core devices of the medium-voltage DC (MVDC) distribution network, interlinking the MVDC system with medium-voltage AC (MVAC) system and low-voltage DC (LVDC) system. With the adoption of the modular multilevel converter (MMC) topology, the isolated MMC (IM 2 C) is a three-port SST sharing one common LVDC-link capacitor. The IM 2 C saves the cost of sub-converter capacitors. However, the existing IM 2 C topology is vulnerable under MVDC fault, with the overcurrent risk of power switches and the malfunction danger of LVDC and MVAC ports. In this paper, an improved hybrid IM 2 C topology is proposed to provide the MVDC fault ride-through (FRT) capability. Using matrix converter topology for sub-converters, the improved IM 2 C is able to generate negative MVDC voltage. An improved FRT control method for three-port modular multilevel converters is also proposed. With the proposed method, the hybrid IM 2 C can control the arm currents and maintain the operation of the LVDC and LVAC ports during the MVDC fault. The simulation results with different MVDC fault locations, fault types and system parameters prove the validity of the proposed topology.
engineering, electrical & electronic