Countermeasure for Converter Transformer Interturn Short-Circuit Faults Using a Resistive-Type SFCL

Zhangheng Liu,Chenguang Yan,Peng Zhang,Zhenfeng Liu,Baohui Zhang
DOI: https://doi.org/10.1109/asemd59061.2023.10369743
2023-01-01
Abstract:In recent years, interturn short-circuit faults have successively occurred in large-capacity converter transformers. The sustaining arc releases a large amount of energy, causing the transformer tank to suffer from continuous overpressure. This study proposes a new countermeasure for converter transformer interturn short-circuit faults by using the resistive-type superconducting fault current limiter (R-SFCL). After the fault occurrence, the R-SFCL will be rapidly put into operation on the grid side of the converter transformer, thus reducing the short-circuit current and the arcing fault energy. Simulation results indicate that the insertion of the R-SFCL can quickly respond to an 8.95% interturn fault and remarkably reduce the circulating current peak by nearly 59.3%. Meanwhile, the fault energy released in 4 cycles also witnesses a significant decrease of 59.6%.