Coordinated Emergency Control of Transient Frequency and Voltage Stability in Sending HVDC System with Wind, Photovoltaic and Hydropower

Wei Li,Xia Yuan,FusuoLiu,Chao Wang,Xiaobin Liang,Jiayu Liu
DOI: https://doi.org/10.1109/EI256261.2022.10116571
2022-11-11
Abstract:component, formatting, style, styling, insert (key words) Abstract—The frequency problem of sending power system caused by the blocking of HVDC could be solved by emergency control of active power, such as cutting off wind or photovoltaic power plants. However, the voltage safety problem may arise after the accident. Firstly, the mechanism of active power emergency control causing voltage out of limit was analyzed, and the integrated emergency control scheme of active power and reactive power control was proposed, taking into account of the coupling of active power and voltage. Then the coordinated emergency control optimization model of HVDC sending system with multiple control measures was established, taking the minimum control cost as the objective and considering the transient voltage and transient frequency security as constraints. Thirdly, the sensitivity method was used to linearize the model, and the successive linear programming method was used to solve it, so as to realize the coordination of continuous and discrete control measures. Finally, the effectiveness of the proposed control scheme and solved strategy was verified by the RTDS simulation results based on the actual case of China northwest power grid.
Environmental Science,Engineering
What problem does this paper attempt to address?