Research on Equivalent Modeling of Offshore Wind Farm VSC-HVDC Transmission System

Qiutong Li,Haishun Sun
DOI: https://doi.org/10.1109/icpet59380.2023.10367498
2023-01-01
Abstract:Most of the existing literature studies the small disturbance oscillation problem of offshore wind farm VSC-HVDC transmission system basing on simplified models. In order to clarify the influence of equivalent modeling on oscillation analysis, this paper first reveals the decoupling characteristics among machine side (MS) offshore station, grid side (GS)-sending end (SE) onshore station, and RE (receiving end) onshore station, and proves the rationality of local subsystem analysis approach. Furthermore, for the GS-SE offshore station and RE onshore station, the feasibility of different modeling schemes is evaluated by calculating eigenvalue deviation. The result shows that when analyzing the oscillation mode of the GS-SE offshore station, MS can be simulated by constant power source, and RE can be simulated by constant voltage source. When analyzing the oscillation mode of the RE onshore station, the SE system can be simulated by constant power source under the premise of retaining the dynamic of the DC submarine cable. The theoretical analysis results are verified by time domain simulation.
What problem does this paper attempt to address?