Sub-synchronous oscillation mitigation of VSC-HVDC with doubly-fed induction generator-based wind farm integration

X. Ma,Y. Lu,J. Tian,C. Zhan,N. Wang,R. Lv,X. Wang
DOI: https://doi.org/10.1049/icp.2023.2392
2023-01-01
Abstract:The interaction between a double fed induction generator based (DFIG) wind farm and a voltage source converter based HVDC (VSC-HVDC) system may cause the risk of a sub-synchronous oscillation near the rated frequency (NRF-SSO), and the SSO occurs frequently in some practical projects. This paper establishes an equivalent system model of DFIGs connected to a VSC-HVDC system. The impedance analytical method is adopted to explore the mechanism of SSO, hence the dominant factors of DFIG and VSC-HVDC impedance in sub-synchronous frequency are studied by simplifying the model. To mitigate the NRF-SSO oscillation, the virtual reactance damping control scheme is proposed to add into the inner loop controller of VSC-HVDC. The influence of damping controller parameters on system stability is studied, and the stability region of parameters is given. Finally, the correctness of the oscillation mechanism and the effectiveness of the damping control strategy are verified by the electromagnetic transient simulation.
What problem does this paper attempt to address?