Experimental Study of Temperature Profile in Underground Corridor of Different Ventilation Conditions Induced by Fire in an Adjacent Compartment

Xiaotao Chen,Xiepeng Sun,Xiaolei Zhang,Xiang Fang,Jiwei Yi,Longhua Hu
DOI: https://doi.org/10.1016/j.tust.2024.106082
IF: 6.9
2024-01-01
Tunnelling and Underground Space Technology
Abstract:Corridor-compartment fire is a fundamental scientific problem in underground space, which is an important transition of fire from compartment to adjacent corridor. The corridor-compartment fire could be divided into two regimes: over-ventilated condition (no flame ejected through the compartment-opening) and under-ventilated condition (the flame ejected through the compartment-opening into the corridor). The research on it is crucial for firefighting and evacuation in the underground space fire scenarios, and the data obtained in this work will be potentially useful to compare with numerical models and further validate their reliability and accuracy for future studies. However, the relevant studies are still very limited for quantifying the temperature evolutions of corridor ceiling flow induced by corridor-compartment fire scenarios for various ventilation conditions (compartment-opening sizes, corridor-opening sizes and corridor widths) as well as fire heat release rates. In this study, a reduced-scale corridor-compartment experimental model is conducted with three compartment-opening sizes, five corridor-opening sizes and seventeen heat release rates. The temperature profile inside the compartment and corridor is measured and analyzed. Results show that: (1) In over-ventilated condition, the maximum temperature in the corridor is determined by the convective HRR and compartment-opening size under the coupling effects of different ventilation conditions. It increases with the HRR and decreases with the compartment-opening size. (2) In under-ventilated condition, the maximum temperature in the corridor is controlled by the coupling effects of different ventilation conditions and HRRs, it increases with the opening size (compartment/corridor-opening sizes) and HRR while decreases with the corridor width. The temperatures of the ceiling flow at the corner between corridor wall and corridor ceiling decreases significantly with the increasing corridor width. (3) A non-dimensional temperature rise model in the corridor which is induced by fire in an adjacent compartment for various ventilation conditions and HRRs is proposed. This model could predict corridor ceiling flow temperature profile for whole fire growth (both over- and under-ventilated conditions) considering different ventilation conditions and HRRs which is induced by a fire in an adjacent compartment.
What problem does this paper attempt to address?