Simulation on Evaporation and Cooling Characteristics of Spray System

Tingting Chang,Chun Wang,Fuqing Wang,Kun Wang
DOI: https://doi.org/10.1088/1742-6596/2599/1/012036
2023-01-01
Journal of Physics Conference Series
Abstract:Abstract This study explored the evaporation and cooling characteristics of air pipeline spray based on computational fluid dynamics method. A geometric model of the pipeline air spray was constructed and meshed, and the Euler-Lagrange research method of the discrete phase model (DPM) was used to study the evaporation and cooling characteristics of the spray system. It was found that the length required for complete evaporation of droplets increased with the relative humidity. When the inlet temperature was 308K and the relative humidity was 40%, the evaporation length increased by 43.71% compared to when it was 20%. There was a negative correlation between the inlet temperature and the evaporation length, and when the relative humidity was 30%, the evaporation length at an inlet temperature of 323K decreased by 1.55m compared to when it was 313K. After spraying, the air temperature gradually decreased along the length of the pipe, and the cooling effect decreased as the relative humidity of the inlet air increased. When the inlet temperature was 308K and the relative humidity was 40%, the outlet temperature was 4.39K higher than when it was 20%, and the cooling effect increased as the inlet air temperature increased. When the relative humidity of the inlet air was 30%, the temperature drop at the outlet at an inlet temperature of 323K was 1.93K higher than when it was 313K.
What problem does this paper attempt to address?