Harmonic Oscillation and Stabilization Strategy of Source-Current-Detected Shunt APF Considering Interaction with Nonlinear Load and Grid Impedance

Yuguo Li,Hao Yi,Fang Zhuo,Xin Jiang
DOI: https://doi.org/10.1109/jestpe.2023.3329171
IF: 5.462
2023-01-01
IEEE Journal of Emerging and Selected Topics in Power Electronics
Abstract:The shunt active power filter (APF) can effectively compensate the harmonics caused by nonlinear loads and improve the power quality. Compared with load current detection, the shunt APF with source current detection is considered to have better harmonic filtering performance. However, the harmonic oscillation caused by APF may occurs when interacted with nonlinear loads and grid impedance but the dynamics of the nonlinear loads are generally ignored in the existing researches. Therefore, this paper built the interaction model of APF, nonlinear loads and grid impedance to investigate the reason and characteristic of the harmonic oscillation. It is found that the harmonics oscillation is prone to happen when the passive resonant frequency of grid impedance and nonlinear loads gets close to the harmonic frequency compensated by APF, besides, the frequency coupling effect caused by the nonlinear loads will lead to symmetric harmonics oscillation. Then a stabilization strategy based on the phase adjustment of vector resonant controller for harmonics detection is proposed. Without affecting the system dynamics, the proposed method can effectively cope with the harmonic oscillation. Finally, simulation and experiment validate the precision of the built models and effectiveness of the proposed method.
What problem does this paper attempt to address?