Complex-Vector Modeling of DFIG-Based Wind Turbine Riding Though Weak AC Grid Voltage Dips

Yufeng Zhang,Hailiang Xu,Shinan Wang
DOI: https://doi.org/10.1007/978-981-33-6606-0_40
2021-01-01
Abstract:Nowadays, wind turbines are required to keep connected and inject reactive current into the faulty grid when a voltage dip occurs at the point of common coupling (PCC). There have been a lot of low voltage ride-though (LVRT) techniques, but few of them concern the stability issue of the wind turbine and the weak AC grid during the fault. To address this issue, this paper established a complex-vector impedance model of the doubly fed induction generator (DFIG) based wind turbines during the LVRT process, considering both the grid- and rotor-side converters (GSC and RSC). In this way, the wind turbine becomes a single-input single-output (SISO) system, which is different from the existing two-dimension scalar models, and hence make it much easier to evaluate the stability of the cascaded system, i.e., the wind turbine and the weak AC grid with residual voltage.
What problem does this paper attempt to address?