Study on DC De-icing Method Based on Uncontrollable 12-Pulse Rectification for Transmission Line

Zongxia Liang
2012-01-01
Abstract:In many de-icing methods for icing transmission lines, DC de-icing method has many advantages when it is compared to the traditional AC or artificial de-icing method, such as smaller power supply capacity, higher efficiency and convenience. This paper studies a DC de-icing method which is based on uncontrollable 12 pulse rectifier. It analyzes DC de-icing principle of uncontrollable 12 pulse rectification. According to the de-icing current of a given conductor, the AC side voltage and the DC de-icing voltage, which could make the ice covering on the conductor de-iced, will be calculated.Then the rated voltage ratio of rectifying transformer can be easily determined, and the icing conductor’s de-icing range is deduced by making the two rectifier bridges connected in series and in parallel. Simulation shows that this method is really efficient to de-ice the ice covering on the transmission line in a certain range. It provides a reliable technology for solving the problem of icing transmission lines.
What problem does this paper attempt to address?