An Anti-icing Method With Switch-off Effect for Glazed Ice on Insulators

韦晓星,贾志东,孙振庭,关志成,许志海,彭向阳
2012-01-01
Abstract:Icing disaster of transmission line and its prevention has become an important and hot problem.A lot of research showed that surface coatings could prevent surpercooled water droplet freezing on the substrates.A new method for anti-icing used for glazed on insulators was proposed based on the thermal method in this paper.Semiconducting silicone rubber(SIR) was painted on the bottom of the insulator without coating on the upper surface.The conductive path was formed when the surpercooled water or droplet covers the area of no coating.And the power loss was limited when there was no precipitation,which was called "switch-off effect".The heat and discharge generated by the leakage current would melt the original ice on the insulator surface.The performance of the insulator string with this kind of coating under freezing rain condition was compared with the string without any coating.Through the analysis and experiment,the method was proved to be effective for anti-icing;while the stability,anti-aging property and configuration should be the focus of further researches.
What problem does this paper attempt to address?