Optimal Meter Configuration Based on Harmonic State Estimation Model and Binary Particle Swarm Optimization

Wei,Hao Yi,Huaying Zhang,Qing Wang,Zebin Yang,Fang Zhuo
DOI: https://doi.org/10.1109/eebda56825.2023.10090766
2023-01-01
Abstract:The monitoring and estimation of harmonic is of great significance to maintain the stable operation of distribution networks. In order to determine the harmonic state level in network and reduce the investment and difficulty of installation, it is necessary to carry out research on the optimization of meter configuration. Therefore, this paper proposes a method of optimal meter configuration combining harmonic state estimation model and binary particle swarm optimization, which aims at estimating all harmonic state variables in the network while using fewer meters. Harmonic state estimation is the process of estimating the harmonic voltage and current state with limited data collected by meters according to the harmonic state estimation model. The rules of state estimation model are established based on the topology connection in network and Kirchhoff's law. IEEE-18 bus network is employed to apply the state estimation model and the result of optimization algorithm shows that only six meters are required to measure and estimate all the harmonic state variables. Finally, the real harmonic values of this network are obtained from Simulink/MATLAB to compare with the estimation values, which verifies the effectiveness of the proposed method.
What problem does this paper attempt to address?