Analysis of Voltage Stability Criterion Considering Load Characteristics

Xinan Zhang
2010-01-01
Abstract:When using the method of Thevenin equivalent tracing to analyze transient voltage stability,which need to consider the effects of nonlinear and dynamic components,the criterion that load equivalent impedance equaling to Thevenin equivalent impedance is usually used to be transient voltage stability critical condition.Based on power flow equations,the paper deduced the criterion,and analyzed the applicability under the constant power factor and other different load characteristics.The results show the criterion is ineffective when the load changes under other characteristics except for constant power factor.The calculation method of voltage stability critical point by constructing correction objective function based on Lagrangian factor was proposed.Finally,two simulation examples proved the conclusions.
What problem does this paper attempt to address?