Abstract:The present article is aimed at reporting its study on the effects of the internal diameter and temperature of the aspiration pipe on the smoke particle transfer. For the study purpose, we measured the smoke particle size distribution and their concentration when they are transferred in the aspiration line of five European standard fire tests by using the Scanning Mobility Particle Sizer in a standard fire testing room. We also analyzed the particle distribution concentration loss and the change of the median particle size so as to know the effect of the aspiration line on the particles' size and their sensitivity. The experimental results indicate that the median smoke particle size of smoldering and pyrolysis fire proves to be smaller than 0.2 μm in the whole combustion process, and after transporting in aspiration line with 5 m and 12 m long, the loss of smoke particle that smaller than 0.1 μm increases with the transport length, and the mean smoke particle size increases several nanometer. The temperature gradient of aspiration tube and smoke aerosol of open fire caused the particle concentration loss increasing due to thermophoretic force, and the median smoke particle size reduces several nanometers. In the early fire during smoldering and pyrolysis, the smoke particle that smaller than 0.1 μm is 15% more of total number concentration, so using short pipe, increasing aspirator speed or staged alarm in aspiration fire detector can reduce the residence time and increase the smoke detection sensitivity.