Comparison Ofaxial Magnetic Field Characteristics Offouraxial Magnetic Field VacuumInterrupter Contacts

Zhongyi Wang,Zhiyuan Liu,Yong Zheng
2006-01-01
Abstract:Magnetic Characteristics ofaxial magnetic field (AMF)offourkindsofvacuuminterrupter contacts are studied with3D finite element method, whichincluded axial magnetic fluxdensity, eddycurrent incontact plates andphaseshift timebetween AMF andsourcecurrent. FourAMF vacuuminterrupter contacts arestudied, which include coil type, cuptype, bipolar typeandquadrapolar type. Theresults showthat: 1)Thestrongest AMF at (a)Coil type (b) Cuptype current peakiswithcoil typecontact. Itfollows bybipolar type,cup type,quadrapolar typewithwhichAMF weakensaccordingly. 2)Theweakest AMF atcurrent zero iswithquadrapolar typecontact. Itfollows bybipolar type, cup type,coiltypewithwhichAMF strengthens accordingly. 3)Theshortest phaseshift timeiswith bipolar type. Itfollows byquadrapolar type, coil type, cup typewithwhichphaseshifttimebecomeshigher accordingly.