Method of determining acceptable air temperature thresholds in Chinese HVAC buildings based on a data-driven model
Heng Du,Zhiwei Lian,Dayi Lai,Weiwei Liu,Lin Duanmu,Yongchao Zhai,Bin Cao,Yufeng Zhang,Xiang Zhou,Zhaojun Wang,Xiaojing Zhang
DOI: https://doi.org/10.1016/j.enbuild.2021.110920
IF: 7.201
2021-06-01
Energy and Buildings
Abstract:<p>Indoor thermal environment design parameters have a significant impact on human thermal comfort, health and building energy consumption. The methods of determining indoor thermal environment design parameters in China and around the world are mainly based on the PMV model. This method often results in certain errors deviations from the actual situation and has difficulty reflecting the differences in the thermal environmental requirements in different climate regions, seasons, building types, etc. This paper proposes a data-driven method based on Chinese Thermal Comfort Database and uses a logistic regression to obtain the indoor air temperature range that 80% of occupants find thermally acceptable under different conditions. The results indicate that the prediction results of this model are in good agreement with the actual data and have as higher accuracy in predicting the satisfaction rate than a linear regression method. This model shows that different regions, seasons, and building types have different acceptable temperature ranges and that the acceptable air temperature ranges are on average 2.0 °C wider than the ISO 7730 and 0.7 °C wider than the GB50736-2012. This method is conducive to the determination of air temperature thresholds and better reflects people's thermal environment needs under different conditions.</p>
energy & fuels,construction & building technology,engineering, civil