Experimental Study on Flashover and Wetting Characteristics of Silicone Rubber Sheet under Different Humidity

Fangzheng Cheng,Xiangjun Zeng,Yongsheng Xu,Haofeng Zhang,Zichen Liu,Fanghui Yin,Liming Wang
DOI: https://doi.org/10.1109/ichve53725.2022.9961674
2022-01-01
Abstract:There is a difference in insulation requirements between indoor and outdoor electrical equipment. So far, there is no unified standard for the insulation design of indoor equipment. In this paper, the development progress of arc is recorded by an ultra-speed camera, and the effects of air relative humidity on flashover voltage and the mass of water absorption are studied. The experimental result shows that with the increase of relative humidity, the U 50 of silicone rubber sheet decreases. There is a positive correlation between the mass of water absorption and the humidity. When the humidity is higher than 79% RH, the local arc is first generated in the area of higher current density and then flashover occurs.