Construction of NaHCO3 fire extinguishing agent modified by fluoroalkyl silane containing short fluorocarbon Chain: Improve its anti-reignition performance

Xia Zhou,Shuanglin Guo,Jun Wang,Yuwei Wang,Renming Pan
DOI: https://doi.org/10.1016/j.tsep.2023.101814
IF: 4.56
2023-01-01
Thermal Science and Engineering Progress
Abstract:To solve the problems of low fire-extinguishing efficiency and inability to resist re-ignition caused by hygno- scopic agglomeration and oil-philic deposition of ultra-fine sodium bicarbonate (NaHCO3) dry powder fire - extinguishing agent, fluorocarbon and flurane structures were introduced on the surface of NaHCO3. With NaHCO3 modificated by short fluorocarbon chains and flurane structures (FCNa-UDFA), the water contact angle (WCA) and oil contact angle (OCA) of FCNa-UDFA are 145.2 degrees and 144.2 degrees, respectively. FCNa-UDFA is of 83.2 % and 79.6 % hydrophobic rate and oleophobic rate, respectively, which indicates that FCNa-UDFA is endowed with enhanced hydrophobic and oleophobic performance. The aviation kerosene oil pool fire and n-heptane oil pool fire can be extinguished by FCNa-UDFA in 0.18 s with average dosages of 19.4 g and 23.1 g, respectively. Hydrophobic and oleophobic modification did not change the chemical fire extinguishing mechanism of FCNa- UDFA which is that NaHCO3 decompose to inhibit gas-phase free radicals. Moreover, after the first extinguishing by FCNa-UDFA, the aviation kerosene oil is fully reignited in 30 s which is significantly longer than that of unmodified Na-UDFA (0.18 s). While, hydrophobic and oleophobic modification can obviously improve the anti - re-ignition performance of FCNa-UDFA due to its physical barrier effect.
What problem does this paper attempt to address?