The effects of single-point extraction on smoke diffusion length and ceiling temperature distribution in a tunnel with one closed end
Shengzhong Zhao,Junhao Yu,Liu Xu,Tiantian Xu,Fei Wang,Imad Obadi,Lin Xu,Wenjun Lei
DOI: https://doi.org/10.1016/j.ijthermalsci.2024.108950
IF: 4.779
2024-06-01
International Journal of Thermal Sciences
Abstract:Previous studies on ventilated tunnel fires mainly focused on both open-end tunnels and longitudinal ventilation. There is still a lack of in-depth research on the effects of single-point extraction on smoke characteristics in tunnel fires with one closed end. In this paper, the effects of heat release rate, smoke vent location, and exhaust volume on smoke diffusion length, maximum ceiling temperature, and temperature attenuation were investigated. The results indicate that smoke diffusion length can be controlled more effectively when the smoke vent is located directly above or downstream of the fire source. The maximum ceiling temperature decreases as exhaust volume increases when the smoke vent is located upstream or directly above the fire source. However, the maximum ceiling temperature is almost unaffected by exhaust volume and smoke vent location when the smoke vent is located downstream of the fire source. Similarly, the effect of exhaust volume on temperature attenuation is also different due to the different smoke vent locations and longitudinal induced air velocities. A series of models are finally proposed to predict the smoke diffusion length, maximum ceiling temperature, and temperature attenuation. The findings could provide reference value for the relevant research and practical engineering application of single-point extraction in tunnels with one closed end.
engineering, mechanical,thermodynamics