Thermal prediction for Air-cooled data center using data Driven-based model

Jianpeng Lin,Weiwei Lin,Wenjun Lin,Jiangtao Wang,Hongliang Jiang
DOI: https://doi.org/10.1016/j.applthermaleng.2022.119207
IF: 6.4
2022-01-01
Applied Thermal Engineering
Abstract:•This work comprehensively compares the temperature prediction performance of six data-driven-based thermal models in steady-state and transient-state scenarios.•Extensive numerical experiments are conducted to explore how sample size, physical layout reconfiguration, and airflow patterns affect thermal model performance.•Four cooling failure transient scenarios are designed to verify the ability of the thermal model to capture the thermal evolution.•XGBoost and LightGBM perform better than other thermal models with RMSE less than 1.0 °C and time overhead less than 10-3 s.
What problem does this paper attempt to address?