Optimized Isolation and Restarting Strategy for UHVDC Converter Faults

L. Shi,D. Ye,Y. Zhang,H. Song,B. Chai,Z. Hao
DOI: https://doi.org/10.1049/icp.2022.1332
2022-01-01
Abstract:As an important method to solve the contradiction between energy distribution and demand, Ultra-high voltage direct current (UHVDC) power transmission has great advantages in long-distance, large-capacity, and cross-regional power transmission scenarios, and has been widely used. Aiming at the problems of long-time consumption, large power outage range, and power loss of the converter fault isolation and restarting process in a UHVDC project, an optimized strategy was proposed based on the analysis of the fault process. On the one hand, the converter protection area, as well as the connection mode of the breakers is optimized, and fast circuit breakers are added to speed up the process. On the other hand, the fault isolation and restarting strategy is optimized. By using the converter phase-shifting control to fast limit the fault current, using fast circuit breaker action to narrow the scope of fault isolation, the occurrence of pole isolation, pole restart, and large-scale machine and load shedding is avoided. Simulation verification shows that the optimized isolation and restarting strategy takes less than 0.5s in total, and only isolates the faulty converter to ensure the continuous power transmission of the unfaulty part, which significantly improves the reliability and economy of UHVDC transmission.