Research on the Temperature Rise Characteristics of Converter Transformer Valve-Side Bushing and the Prediction Model of Full State Index

M. Lin,K. Liu,Z. Ding,H. Tang,Y. Yang,G n. Wu
DOI: https://doi.org/10.1049/icp.2022.0453
2021-01-01
Abstract:The valve-side bushing of UHV converter transformer carries a large multi-frequency superimposed current, and it is prone to local overheating faults such as the copper-aluminum transition zone and the contact finger ablation of the strap. In order to verify the temperature rise characteristics of the valve-side bushing of the converter transformer, the thermal performance test system of UHV DC bushing is established in this paper. The thermal performance test method of UHV DC bushing with high ambient temperatures and multi-frequency current was put forward, and the temperature rise test was carried out. The results show that the axial and radial temperatures inside the valve-side bushing core of the converter transformer are unevenly distributed, and the temperature distribution of two types of paper-impregnated capacitive DC bushings has the characteristics of a typical first-order exponential function under the conditions of high ambient temperature and multi-frequency current. Based on the experimental results, this paper establishes a model of the axial and radial heat balance characteristics of the inner core of the bushing capacitor under multi-frequency current. The model can be used as the steady-state temperature criterion of the bushing, which has important guiding significance for the operating state monitoring of the bushing.
What problem does this paper attempt to address?