Resonance Characteristic Analysis of Flexible DC Distribution Network

K. Cui,L. Qu,Z. Yu,W. Zhou,R. Zeng
DOI: https://doi.org/10.1049/icp.2020.0391
2021-01-01
Abstract:The use of large number of complex and non-linear power electronic equipment in DC distribution networks will inevitably bring a series of harmonic problems to the system. One of which is called harmonic instability, which is caused by resonance in the DC system. In this paper, the basic topology of DC distribution network and the reasons for harmonic instability is analyzed, then, based on the switch function theory, the calculation formula of the DC side harmonic impedance of MMC, which is the core equipment of DC distribution network, is derived. Finally, taking a typical flexible DC power distribution demonstration project as an example, the DC side harmonic impedance of MMC is analyzed and the analysis results are verified by PSCAD simulation. Verification results show that, the calculation model can accurately calculate the harmonic impedance of the DC distribution network, which is of reference value for managing harmonic content and avoiding harmonic instability.
What problem does this paper attempt to address?