F-P Ultrasonic Sensor Based on Three-Beam Support Cantilever Structure

Kejie Wu,Weigen Chen,Zhixian Zhang,Yuxuan Song,Fan Liu,Tianhe Yang
DOI: https://doi.org/10.1109/aeero52475.2021.9708166
2021-01-01
Abstract:Based on the principle of F-P (Fabry-Perot) interference, this paper designs a three-beam support cantilever optical fiber F-P sensor. Three beam support cantilever structure improves the sensitivity of detecting GIS partial discharge, ensures the consistency of the insulation medium inside and outside the sensor, and eliminates the influence of temperature changes on the sensor. Based on COMSOL simulation, this paper analyzes the influence of the beam width on the resonance frequency and static pressure sensitivity of the three-beam support cantilever structure, and selects the optimal parameters to design a F-P sensor with a resonance frequency of 27033 Hz. Based on the optical detection platform, this paper uses Electric ignition to simulate partial discharge ultrasonic signals in the air. The measured resonance frequency of the sensor is 28077 Hz. The sensor can effectively detect the ultrasonic signal of partial discharge of GIS.
What problem does this paper attempt to address?