Experimental Investigation on the Improvement of Cooling and Dehumidification of a Direct-Expansion Terminal Integrated with Flat Heat Pipe

Hengxin Zhao,Yifan Wu,Borong Lin,Hongli Sun
DOI: https://doi.org/10.1016/j.enbuild.2022.111922
IF: 7.201
2022-01-01
Energy and Buildings
Abstract:Low energy efficiency and draughts of traditional convection cooling terminals led to the development of radiant cooling terminals; however, they have insufficient cooling capacity and surface condensation or poor dehumidification ability. In this study, we develop a novel direct-expansion terminal by combining a flat heat pipe and an air source heat pump, resulting in a larger cooling capacity, faster cooling speed, and strong adjustability in dehumidification. The cooling capacity of the proposed novel terminal is between 1160 and 2600 W, and the maximum cooling capacity is 2.24 times that of pure radiation. Additionally, the structure optimization enables the proposed terminal to separate the sensible heat and latent heat and adjust dehumidification, demonstrating dynamic and flexible characteristics. Moreover, it meets the demands of part-time and part-space cooling. The indoor humidity ratio experiences a change of between 2.8 and 7.9 g/kg after dehumidification, and the indoor relative humidity can be reduced to a comfortable range in summer within 30 min by adjusting the compressor opening degree. The novel terminal considers the advantages of radiant and convection terminals, and provides opportunity for the future improvement of cooling terminals.(c) 2022 Elsevier B.V. All rights reserved.
What problem does this paper attempt to address?