Improved Firing Angle Control for Mitigating Continuous Commutation Failure of HVDC System

Chengxiang Yang,Lingrao Wang,Wei Yao,Chenghao Li,Dongxue Gao,Jinyu Wen
DOI: https://doi.org/10.1109/ispec50848.2020.9351046
2020-01-01
Abstract:The continuous commutation failure (CCF) of high-voltage direct-current (HVDC) transmission system will cause consecutive impacts to the AC-DC hybrid power system. This paper proposes an improved firing angle control strategy with the DC power recovery rate and AC fault severity considered to suppress CCF. The dominant factors and mechanism of CCF are analyzed. Then, the method of dynamically adjusting firing angle according to the DC power recovery and AC voltage drop is introduced. During the fault recovery after first commutation failure, firing angle of the inverter side can be adaptively reduced to improve commutation margin. Case studies based on the CIGRE benchmark model validate the effectiveness of the proposed control strategy.
What problem does this paper attempt to address?