Experimental Study and Model Analysis of Flashover in Confined Compartments

Ruowen Zong,Ruxue Kang,Weifeng Zhao,Changfa Tao
DOI: https://doi.org/10.1007/978-981-10-0376-9_66
2016-01-01
Abstract:Catastrophe analysis of flashover has been studied based on a series of fire experiment in three different scales of compartment. The experimental data have been compared with the theoretical values predicted by a nonlinear fire growth model, which were in reasonable agreement with the theoretical bifurcation curves. Several critical conditions for flashover to occur have been also investigated, including the ceiling height, the fire radius, and the compartment scale size. The results showed that fire radius played the dominating role in the occurrence of flashover, and the characteristic value of fuel, χH c /H vap , could be regarded as the dominating factor for the width of unstable range at the theoretical curves. And the scaling correlation between the compartment size and the critical fire radius appeared to be \( {R}_f\propto {L}_c^{3/4} \) from the tests.