Investigation on the Regeneration Performance of a New Mixed Liquid Desiccant Solution in Falling Film Regenerator

Tao Wen,Dan Zhong,Yuanhao Wang,Yimo Luo
DOI: https://doi.org/10.3390/proceedings2221374
2018-01-01
Proceedings
Abstract:The present study firstly developed a new kind of mixed liquid desiccant for the purpose of causticity reduction on metal based regenerator. The formula of the mixed liquid desiccant is 25% LiCl + 39% hydroxyethyl urea + 36% water. Experimental results show that the causticity of the mixed solution is much less severe than that of conventional LiCl solution. The regeneration rate increases with the increase of air flow rate and solution temperature and decreases with the increase of air inlet humidity. The air temperature and solution flow rate has negligible influence on the regeneration performance. The present study provides a practical alternative for the selection of liquid desiccant and also give useful guidance for the design of regenerator.
What problem does this paper attempt to address?