An Automatic Data Acquisition Device for Transformer Oscillating Switching Impulse Voltage Tests

Meichun Huang,Zhaohui Li,Weiming Ouyang,ChunLei Li,Lisheng Pang
DOI: https://doi.org/10.1109/ICSAI53574.2021.9664158
2021-01-01
Abstract:The oscillating switching impulse voltage test plays important role in the assessment of transformers. An automatic data acquisition device is developed for this test. Four synchronous A/D conversion channels with 12 bits resolution and up to 10 MHz sampling rate for each channel are assigned to acquire the voltages at the both sides of the tested transformer as well as the currents at the neutral...